Small loggers at the last taps, checked against the scheme's own schedule, with every miss sent to the person who can fix it.

Loggers record when water reaches the tail and at what pressure, the pump run is logged at the head, TailEnd gives each supply window a verdict, and the Junior Engineer gets a task with the likely cause whenever the tail misses out.

01In one minute

Four steps, from the last tap to a fix

02What changes

Today, and with TailEnd

Today
With TailEnd
Did the tail get water?
Known from complaints, visits and operator feedback.
Recorded for every supply window at the tail points, and shown as kept or missed.
Regularity
Measured every two years in a sample survey.
Windows kept at the tail, every day, using the same "as per schedule" idea.
Pressure
Seen at the source and on SCADA schemes.
Minutes above the threshold at the last tap, in each window.
Chlorine at the farthest tap
Tested by hand when a kit and a visit coincide.
Tested weekly by the Jal Mitra, read from a photo, low readings sent to the AEE.
When something goes wrong
A complaint, then a search along the line.
A task for the JE with the trace, the likely causes and a checklist; closed with what was found.

The "Today" column is drawn from the challenge statement and the 2024 Functionality Assessment for Assam. We'll walk through the real process with a PHED division during discovery.

03The challenge, point by point

What the Department asked for, and where to see it

The challenge asks forWhat TailEnd does
A low-cost, scalable way to verify service at representative points, without household metersBattery loggers on stand-posts or consenting households' spare taps at the tail and on high ground; a few fixed, the rest rotating every two weeks.See it
Simple indicators: availability, duration and continuity, pressure compliance, water-quality status, abnormal-event alertsPer window and per week: supply days, windows kept, minutes at pressure, chlorine at the farthest tap, and events.See it
Drill-down for field actionDivision → scheme → point → window, ending in a task for the JE with the trace and likely causes.See it
Objective verification of actual deliveryReadings come from the logger at the tap, not from reports. The head logger or SCADA shows what was sent.See it
Early identification of low-pressure or interrupted areasA missed window raises an event within minutes of the window ending; a run of late windows goes on a watch list.See it
Faster response and better accountabilityEach event has a named officer, a clock and a closure note. The EE sees time to fix by scheme.See it
Minimally intrusive, low-maintenance, suitable for intermittent communicationNothing inside homes; designed to run for months on a battery; readings are stored and sent in bursts when a signal is found.See it
Detailed breakdownWindow rules and indicators · Likely causes · Workflows · The logger · Architecture and security · Discovery
ARules and indicators

When a window counts as kept

TestRule (starting point)Why
On timeWater at the tail within 30 minutes of the window's startPeople plan around the announced time
Long enoughWater for at least 75% of the windowA short window means households fill less
Enough pressureAt least 70% of those minutes above 7 m of head (0.7 bar)Below that, a tap on a raised platform barely runs

What the indicators mean

IndicatorMeasured as
Supply availabilityDays in the week with any water at the point
Duration and continuityMinutes with water per day; breaks within a window
Pressure complianceShare of minutes with water above the threshold
RegularityWindows kept, of those scheduled
Water-quality indicatorResidual chlorine at the farthest tap, weekly; 0.2 mg/L or more counts as present

How a likely cause is suggested

Pattern in the readingsLikely cause
Pump ran the full window, head normal, tail low throughoutValve partly closed or wrongly set on that branch
Head pressure falls while the pump runs; nearby points also lowLeak or burst on the line
Tail fine at the start, falls as the window gets busyDraw upstream, such as booster pumps on connections
Water arrives late, in spurts, after the line was emptyAir lock
Pump ran less than the windowSupply cut short at source: power or operation

These rules and thresholds are starting points. PHED sets the real ones. Causes are suggestions in order of fit; the Junior Engineer records what they actually find, and those records are used to improve the order. The only automated reading is the chlorine comparator photo, and the Jal Mitra confirms every figure.

BWorkflows

A missed window, from the tap to a fix

Logger
Records the window
When water came, for how long, at what pressure. Sends when it has a signal.
TailEnd
Gives a verdict
Kept or missed against the schedule, compared with the pump run and the head.
AEE
Sends it out
The event goes to the JE with the trace and likely causes, or to the Pani Samiti if it's theirs.
JE
Finds and fixes
Works through the checklist, records the cause and action, asks for a test run.
TailEnd
Checks it worked
The test run and the next window show whether the tail is back to schedule.

Chlorine at the farthest tap

Jal Mitra, weekly
Tests at the tail
Standard comparator kit at the most distant tap.
Phone
Reads the photo
Colour matched against a printed reference card; the Jal Mitra confirms.
TailEnd
Checks the level
Below 0.2 mg/L becomes an event for the AEE with dosing advice.
WQMIS
Keeps the record
Reading and photo prepared for upload in the WQMIS format.
CLogger and architecture

A simple device, a field app, one set of records

What the logger does

Reads pressure every minute while water is present and every 15 minutes otherwise. Stores several weeks on board. Sends a short burst by GSM after each window and on events; LoRa to a village gateway where GSM is weak.

How it is fitted

On a T-joint with an isolation valve below a public stand-post or a spare tap, in a sealed, lockable box. Fitting is a short job for one plumber. Nothing is fitted inside a home.

What we still have to prove

Unit cost, battery life and sealing through a monsoon are design targets. Two hardware iterations are planned, with Dr Rupam Goswami's review.

Why not household meters

The challenge rules them out, and they aren't needed: a handful of well-placed points shows whether the tail is served.

People
Jal Mitras
Junior Engineers
AEEs and EEs
Pani Samiti
Devices and apps
Tail and head loggerspressure, battery, GSM or LoRa
Android field appoffline, Assamese and English
Web app for engineers
Core
Window verdicts
Cause suggestions
Events and tasks
Chlorine photo reader
Audit logappend-only
Data
PostgreSQL + PostGISpoints, pipelines
Reading time series
Photo storage
Connects to
SCADAwhere available
WQMISchlorine readings
JJM Assam grievances
SMS gateway

Our live platform runs the same roles, approvals, photo capture and notifications engine. It can be hosted on the State Data Centre or a MeitY-empanelled cloud.

Access by role

Jal Mitras see their scheme, JEs their section, AEEs and EEs their sub-division or division. Officers sign in by OTP.

Nothing is overwritten

Readings, verdicts, tasks and closures are logged with who, when and which device.

Households' privacy

A household hosting a logger signs a consent form and can withdraw. Names and numbers are kept to the minimum and masked in reports (DPDP Act 2023).

Devices that are hard to tamper with

Sealed boxes, tamper and battery alerts, and a logger that goes silent becomes an event of its own.

DDiscovery

What we'll settle with the Department in the first three weeks

The design rests on the challenge statement, the 2024 Functionality Assessment and public information on JJM systems. These are the points we'll confirm with a PHED division before building the production system.

  • The pilot scheme, its pipeline map and its announced supply schedule.
  • Where the tail and high-ground points are, walked with the JE and the Jal Mitra.
  • The pressure threshold and the window rules PHED wants to use.
  • Whether pump status comes from SCADA or from the Jal Mitra's log on that scheme.
  • The WQMIS upload route for tail-end chlorine readings.
  • Who acts on each kind of event where O&M sits with the Pani Samiti.